Air Source Heat Pump
The system reduces the emission of particulate matter, odors and ammonia from pig farms.
keywords:
Category:
Heater
Air source heat pump (chilled water) unit is a central air-conditioning unit that uses air as the cooling and heating source and water as the refrigerant carrier. Air source heat pump unit with 35KW, 65KW, 80KW, 130KW, 1 60KW as the base module, to achieve any combination of 16 modules, forming a combination of products within the range of 35KW-2560KW, with environmental protection, simple installation, flexibility, moderate investment, short construction period, etc., and is now more and more widely used in animal husbandry industry.
Standard air heat source pump (chilled water) technical parameters table
| Product Model | AWK35*-1 | AWK65*-1 | AWK130*-1 | ||||
| Name Refrigeration | Cooling Capacity | KW | 33 | 65 | 130 | ||
| Rating Power | KW | 10.5 | 20.2 | 40.5 | |||
| Energy Efficiency Ratio (oop) | / | 3.14 | 3.22 | 3.21 | |||
| Name Heating | Calorimetric | KW | 35 | 70 | 140 | ||
| Rating Power | KW | 10.6 | 20.9 | 41 | |||
| Maximum Current | A | 25 | 50 | 100 | |||
| Type of Power Supply | - | 3N-380V/50Hz | |||||
| Operation Control Mode | - | Fully Automatic | |||||
| Compactor | Typology | - | Scroll Compressor | ||||
| Quantity | EA | 1 | 2 | 4 | |||
| Air-side Heat Exchanger | Heat Exchanger Type | - | Split-barrier (corrugated) Fins + High-efficiency Internally Threaded Steel Tubes | ||||
| Fan Type | - | Axial Fans | |||||
| Fan Power | KW | 0.85 | 0.85x2 | 2.2x2 | |||
| Number of Fans | EA | 1 | 2 | 2 | |||
| Water-side Heat Exchanger | Typology | - | Shell and Tube Heat Exchanger | ||||
| Bear the Weight | Mpa | 1 | |||||
| Water Flow | M3/h | 5.7 | 11.2 | 22.4 | |||
| Pipe Diameter | - | DN32 | DN50 | DN65 | |||
| Water Pressure Loss | kpa | 50 | 50 | 50 | |||
| Refrigerant | Formality | - | R410a(R22) | ||||
| Filling Capacity | kg | 6 | 11 | 22 | |||
| Scope of Operation | - | Outdoor temperature: cooling 18~48°C/heating -15~25°C | |||||
| Hot and cold water outlet temperature: cooling 4~15°C/heating 23~55°C/heating 23~55°C (65°C) | |||||||
| Safety Protection | - | High and low pressure protection, exhaust vapor humidity protection, water cut-off protection, anti-freezing protection, fan overheating protection, press overcurrent protection, phase shortage and phase sequence protection, etc. | |||||
| Net Dimension | Lenght | mm | 1155 | 2250 | 2400 | ||
| Width | mm | 860 | 860 | 1150 | |||
High | mm | 1856 | 1856 | 2250 | |||
| Unit weight (net) | kg | 300 | 560 | 1060 | |||
| Product Model | AWK35* | AWK65* | AWK80* | AWK130* | AWK160* | ||
| Nominal Refrigeration | Cooling Capacity | KW | 33 | 65 | 75 | 130 | 150 |
| Rating Power | KW | 10.5 | 20.1 | 23.3 | 40.2 | 46.7 | |
| Energy Efficiency Ratio (oop) | / | 3.14 | 3.23 | 3.22 | 3.23 | 3.22 | |
| Nominal Heating | Calorimetric | KW | 35 | 70 | 80 | 140 | 160 |
| Rating Power | KW | 10.6 | 20.9 | 23.5 | 41 | 47 | |
| Nominal Heating at Low Temperatures | Calorimetric | KW | 23 | 45 | 50 | 90 | 100 |
| Rating Power | KW | 9.6 | 18.8 | 20.8 | 37.5 | 41.7 | |
| Maximum Current | A | 25 | 50 | 65 | 100 | 130 | |
| Type of Power Supply | - | 3N-380V/50HZ | |||||
| Operation Control Mode | - | Fully Automatic | |||||
| Compactor | Typology | - | Scroll Compressor | ||||
| Quantity | EA | 1 | 2 | 2 | 4 | 4 | |
| Air-side Heat Exchanger | Heat Exchanger Type | - | Slit (corrugated) fins + High-efficiency internally threaded copper tubes | ||||
| Fan Type | - | Axial Fans | |||||
| Fan Power | KW | 0.85 | 0.85x2 | 0.85x2 | 2.2x2 | 2.2x2 | |
| Number of Fans | EA | 1 | 2 | 2 | 2 | 2 | |
| Water-side heat exchanger | Typology | - | Shell-and-tube heat exchanger | ||||
| Bear the pressure | Mpa | 1 | |||||
| Water flow | m3/h | 5.7 | 11.2 | 13 | 22.4 | 26 | |
| Pipe diameter | - | DN32 | DN50 | DN65 | DN65 | DN80 | |
| Water pressure loss | kpa | 50 | 50 | 50 | 50 | 50 | |
| Refrigerant | Formality | - | R410a(R22) | ||||
| Filling Capacity | kg | 6 | 11 | 13 | 22 | 26 | |
| Operating Range | - | Outdoor temperature: cooling 18~48°C/heating -25~25°C | |||||
| Hot and cold water outlet temperature: cooling 4~15°C/heating 23~55°C (65°C) | |||||||
| Security Protection | - | High and low pressure protection, exhaust vapor humidity protection, water cut-off protection, anti-freezing protection, fan overheating protection, press overcurrent protection, phase shortage and phase sequence protection, etc. | |||||
| net size | Length | mm | 1155 | 2250 | 2250 | 2400 | 2400 |
| Width | mm | 860 | 860 | 860 | 1150 | 1150 | |
| High | mm | 1856 | 1856 | 1856 | 2250 | 2250 | |
| Unit weight (net) | kg | 300 | 560 | 585 | 1060 | 1110 | |
CONTACT US
Address
No. 28 Road, Beian Industrial Park, Jimo District, Qingdao City, Shandong Province
What makes us different from other providers?
Committed to providing comprehensive technical support and solutions for livestock and poultry breeding industry
Professional skills
We have a professional technical team and rich practical experience in the fields of farm planning and design, EPC equipment supply, installation and delivery.
The company has independent research and development capabilities and can provide customers with advanced, efficient, and stable products and solutions
Rich product variety
Our main business covers environmental control systems, automatic feeding systems, fence system equipment, indoor drinking water system equipment, etc. We have a wide variety of products to meet the needs of different customers
Quality advantage
The company focuses on product quality management and has passed the ISO9001 product quality management certification system to ensure that the quality and performance of products meet national standards
Interested in our product
Enter your contact information and we will contact you as soon as possible
Project Case
FAQ
Where is your factory?
Our factory is loacated in Qingdao city, Shandong provice, Chian and which has a very mature livestock equipment industry chain.
What certificates do you have?
We are ISO 9001, and national High-Tech company certificated and Fiberglass Fan are CE certificated.
Can I get some samples?
Yes, you can contact us for samples.
Are you a factory or trading company?
We are a intergrated manufacturing and sales company.
What is the MOQ of the product and what is the production leadtime after ordering?
You can conatact us for MOQ and usually leadtime is 15-30days since ordering.
What are the payment options?
T/T payment is preferred.
Product recommendation
We focus on producing and offering feed system, ventilation and cooling system and environment control system, and we also engages in the farm design, product manufacturing and construction of modernized farms for livestock and poultry.
SEEK18- SEEK36 Direct Drive Series
SEEK36- SEEK55 Belt Type Series